GB200/GB300/Vera Rubin Emulator
- Application Scenarios for Air-Liquid Hybrid Load Bank
- Liquid-Cooled Data Center Infrastructure Validation: Designed for pre-deployment verification, joint commissioning, and acceptance of next-generation liquid-cooled data centers and AI computing platforms.
- Liquid-Cooled Rack Architecture Compatibility: Fully compatible with advanced liquid-cooled rack architectures, including NVIDIA GB200, Rubin, and OCP ORV3.
- Air-Liquid Collaborative Cooling Test: Simulates dual air and liquid cooling within a single enclosure, accurately replicating the operating environment of high-power-density servers.
- Server-Free Load Simulation: Emulates the thermal load and power fluctuations of high-power compute nodes without requiring actual GPU servers.
- Liquid Cooling System Joint Commissioning: Ideal for joint commissioning and stress testing of liquid cooling loops, including CDUs, piping networks, quick-connect interfaces, and dry coolers.
- Power Distribution & Backup System Validation: Supports full-load testing and cable aging tests for power distribution systems, UPS, and backup generators.
- Facility Air Cooling System Validation: Tests precision air conditioning, air-cooled terminals, and hybrid air-liquid cooling operating conditions within the data center.
- Performance Calibration & PUE Calculation: Conducts performance calibration of liquid cooling systems, PUE calculations, and operational stress validation.
- Proactive Risk Identification: Identifies potential hazards such as insufficient pipeline resistance, flow rate matching deviations, power distribution capacity bottlenecks, and inadequate cooling margins.
- High-Density Cluster Deployment Assurance: Provides comprehensive testing assurance to ensure the safe and stable deployment of high-density computing clusters.
- Parameter Table
|
Product Model (Voltage Customizable) |
LB-208KW-AC380V |
LB-216KW-AC380V |
LB-240KW-AC380V |
LB-280KW-AC380V |
LB-354KW-AC380V |
|
Rated Power |
208kW |
216kW |
240kW |
280kW |
354kW |
|
Liquid Cooling Power |
160kW |
168kW |
192kW |
250kW |
322kW |
|
Air Cooling Power |
48kW |
48kW |
48kW |
30kW |
32kW |
|
Rated Voltage |
AC380V |
AC380V |
AC380V |
AC380V |
AC380V |
|
Load Resolution |
1kW |
1kW |
1kW |
1kW |
1kW |
|
Reference Dimensions |
600*1200*2300mm |
600*1200*2300mm |
600*1200*2300mm |
600*1400*2300mm |
600*1400*2300mm |
|
Cooling Method |
Liquid Cooling、 Air Cooling |
Liquid Cooling、 Air Cooling |
Liquid Cooling、 Air Cooling |
Liquid Cooling、 Air Cooling |
Liquid Cooling、 Air Cooling |
|
Reference Weight (kg) |
650 |
650 |
750 |
650 |
850 |